SPEDLPX0205REN
5
DIALOG PLUS
− Programmable timer:
This function enables the user to program the timer to automatically switch the system on or off at specific
times (configurable via the software).
− Stand by:
During Stand-by function the inverter is switched off and the batteries are charged. The stand-by function is
automatically activated when the UPS is switched off.
− Frequency auto selection:
The UPS can be configured to automatically select the output frequency (50 or 60Hz), by using the input
frequency as its reference (50 or 60Hz).
− Battery start-up (cold start):
The UPS can be switched on even when no incoming mains supply is available.
− Auto restart:
Following a mains supply failure, once the UPS has shutdown upon reaching the end of its designed battery
autonomy time, the system can be configured to automatically restart once the incoming mains supply
returns (configurable via the software).
− GS/TÜV certified:
The Dialog Plus range has been tested and approved by the official certification agency GS/TÜV which
guarantees the products performance and reliability.
− Network, phone and computer protection:
The UPS provides overvoltage protection via the RJ11 and RJ45 connectors.
− Re-settable input protection:
The UPS input is connected via a re-settable fuse to protect against overloads or short circuits.
Low consumption
− Low impact on the mains power supply (sinusoidal absorption):
The input current absorbed by the UPS from the mains supply is sinusoidal. This means that the system has a
very low impact on the incoming mains supply network, and as a consequence, on the other electrical
devices that are connected to it.
− Load power factor correction (UPS input power factor close to 1):
The UPS absorbs power from the incoming mains supply with a power factor close to 1, even if the systems
supplied by the UPS have a power factor inferior to this. For example, if the UPS supplies a piece of IT
equipment with an input power factor of 0.65, the UPS input power factor will still remain close to 1,
ensuring that any mains supply power factor correction banks are not overloaded.